主  题:Circuit faults Circuit breakers Phase change materials Fault currents Power electronics Switches Equivalent circuits Circuit breakers (CBs) dc-dc power converters hybrid circuit breaker (HCB) medium-voltage dc (MVdc) power distribution faults power electronics shipboard power system (SPS) solid-state circuit breaker (SSCB) 

摘      要:In this article, an active fault current sharing (FCS) strategy is proposed to improve the dc circuit breaker (CB) operation in a breaker-based medium-voltage dc (MVdc) system. The peak turn-off current of CBs can be decreased by controlling the existing converters located in parallel with activated CBs to share the fault current. This reduction effect can be amplified from the systematic perspective since one single converter with the proposed FCS can benefit different CBs in various fault scenarios. The short-circuit fault scenarios of a shipboard breaker-based MVdc system are analyzed and the corresponding fault equivalent circuits, including power converters adjacent to CBs, are developed. The device stress of voltage-fed (VF) and current-fed (CF) converters applying the proposed active FCS strategies during short-circuit faults is derived and compared with those of passively shutdown counterparts. Finally, a downscaled experimental test bed was built to emulate a 6-kV/6-MW MVdc system fault scenarios. The experimental results are provided to verify the proposed FCS.

读者评论 与其他读者分享你的观点

用户名:未登录
我的评分