文献详情 >Voltage Sag Monitor Placement ... 收藏

Voltage Sag Monitor Placement for Fault Location Detection Based on Precise Determination of Areas of Vulnerability

作     者:Mojtaba Hajiahmadi Rahmat-Allah Hooshmand Arash Kiyoumarsi 

作者机构:Department of Electrical EngineeringFaculty of EngineeringUniversity of IsfahanIsfahanIran 

出 版 物:《Journal of Modern Power Systems and Clean Energy》 (现代电力系统与清洁能源学报(英文))

年 卷 期:2025年第13卷第1期

页      面:228-240页

核心收录:

学科分类:080802[工学-电力系统及其自动化] 0808[工学-电气工程] 08[工学] 

主  题:Area of vulnerability(AOV) false position method(FPM) fault location detection(FLD) power quality voltage sag monitor(VSM). 

摘      要:The increase in the number of sensitive loads in power systems has made power quality,particularly voltage sag,a prominent problem due to its effects on consumers from both the utility and customer ***,to evaluate the effects of voltage sag caused by short circuits,it is necessary to determine the areas of vulnerability(AOVs).In this paper,a new method is proposed for the AOV determination that is applicable to large-scale *** false position method(FPM)is proposed for the precise calculation of the critical points of the system ***,a new method is proposed for the voltage sag monitor(VSM)placement to detect the fault locations.A systematic placement scheme is used to provide the highest fault location detection(FLD)index at buses and lines for various short-circuit fault *** assess the efficiency of the proposed methods for AOV determination and VSM placement,simulations are conducted in IEEE standard *** results demonstrate the accuracy of the proposed method for AOV *** addition,through VSM placement,the fault locations at buses and lines are detected.

读者评论 与其他读者分享你的观点

用户名:未登录
我的评分