作者机构:Tsinghua Univ Dept Elect Engn Beijing 100084 Peoples R China Beijing Sifang Automat Co Ltd Beijing 100085 Peoples R China Univ Durham Sci Labs Sch Engn Durham DH1 3LE England
出 版 物:《IET GENERATION TRANSMISSION & DISTRIBUTION》 (IET Gener. Transm. Distrib.)
年 卷 期:2008年第2卷第6期
页 面:789-799页
核心收录:
主 题:Scheme Power cables Stuck at faults current capacity Source impedance Shunt reactors Transmission Lines distributed parameter
摘 要:The authors describe the principle of an online fault-locating scheme using the voltage and current synchronously sampled from both ends of a long EHV/UHV transmission line. This is based on a distributed parameter model of the line. Steady-state transmission line equations are used to construct a fault-locating function, with the effect of distributed capacitive current taken into account. Application is extended to practical situations where in-line shunt reactors are present for compensation. The fault-locating scheme is insensitive to fault path resistance, fault inception angle, load current and source impedance. Test results verify the high accuracy and speed of the scheme for different types of faults.