版权所有:内蒙古大学图书馆 技术提供:维普资讯• 智图
内蒙古自治区呼和浩特市赛罕区大学西街235号 邮编: 010021
作者机构:State Key Laboratory of Control and Simulation of Power Systems and Generation EquipmentDepartment of Electrical EngineeringTsinghua UniversityBeijing 100084China
出 版 物:《Protection and Control of Modern Power Systems》 (现代电力系统保护与控制(英文))
年 卷 期:2017年第2卷第1期
页 面:111-121页
学科分类:080801[工学-电机与电器] 0808[工学-电气工程] 08[工学]
基 金:the National Natural Science Foundation of China(Grant No.51120175001) Science and Technology Project of State Grid Corporation of China(GWKJ2013-005)
主 题:CT modeling Air gap Preisach Theory Saturation Remanence
摘 要:Current Transformer(CT)modeling,by which CT’s characteristics can be studied has a significant importance in CT selection and *** spite of numerous studies about closed-core CT model,only a few works have been conducted on air-gapped ones with the following problems:models of which required data is easily-accessible,have poor simulations of magnetization process;on the contrary,models which have satisfactory simulations,are hard to be established because of the hard-to-get required ***,based on Preisach Theory,a novel air-gapped CT model is deduced from the closed core CT *** proposed model is accurate and can be established *** saturation and remanence properties of closed-core CT and air-gapped CT are simulated and compared.