The demand for high-speed protective relaying in modern power grids is growing. A relay's fast and secure operation to clear faults is critical, especially for EHV/UHV transmission systems (400 kV and above). This...
详细信息
The demand for high-speed protective relaying in modern power grids is growing. A relay's fast and secure operation to clear faults is critical, especially for EHV/UHV transmission systems (400 kV and above). This research proposes a sub-cycle distance relaying, which is based on the least error squares (les) method, and with a data interface module implemented on field programmable gate array (FPGA). Taking advantage of inherent parallelism and pipelined architecture of the FPGA, the proposed relay design can support real-time data communications. Also, the flexible and reliable feature of the les algorithm allows the proposed relay to make a fast and secure trip decision in different scenarios. The case studies demonstrate the effectiveness of the les-based relay.