Dynamic equivalentmodelling for wind power plant (WPP) has become an important tool to analyse the grid integration characteristics of large-scale WPPs. Owing to the large differences of operational performance betwe...
详细信息
Dynamic equivalentmodelling for wind power plant (WPP) has become an important tool to analyse the grid integration characteristics of large-scale WPPs. Owing to the large differences of operational performance between wind turbines, multi-machine equivalentmodel is more accurate to represent the WPP. In order to determine the generator parameters of multi-machine equivalentmodel, this study proposed a multi-machine equivalentmodelparameteridentificationmethod for DFIG-based WPP only with data measured at the point of common coupling. On the basis of established clustering model, it is explained how the measurement data are properly processed for use as the input of parameteridentification considering the collecting circuit and the estimated instantaneous power of equivalent wind turbine. The developed parameter determination method is tested against a large-scale plant model, and simulation results confirm the effectiveness of the method.