This study proposes a particlefilter (PF)-baseddualestimationmethod for tracking the dynamic states of a synchronous generator. The authors consider the situation where the field voltage measurements are not readi...
详细信息
This study proposes a particlefilter (PF)-baseddualestimationmethod for tracking the dynamic states of a synchronous generator. The authors consider the situation where the field voltage measurements are not readily available. The PF is modified to treat the field voltage as an unknown input which is sequentially estimated along with the other dynamic states. To exploit the tracking results from the estimator, the authors consider the application of use the estimated field voltage to identify internal failures in the excitation subsystem. The proposed method is tested on a 10-machine, 39-bus system to assess selectivity between estimation for regular external disturbances and both physical failure, and modelling abnormality within excitation system. The presented studies show that the proposed method (i) provides reasonable tracking results for the dynamic states and the field voltage simultaneously, (ii) rapidly tracks minor excitation loss due to exciter internal failure while maintaining selectivity and (iii) is robust to measurement noise.