A new data-mining method for assessment of the ability of bidding units is proposed in this paper. The algorithm of reducing attribute value is introduced to get minimum rules. An example which considers the various f...
详细信息
The aim of relay protection is to isolate the fault zone or device and guarantee the systemsecurity. The primary protection and backup protection is in cooperation relationship, and backup one could not be canceled b...
详细信息
ISBN:
(纸本)9780889869059
The aim of relay protection is to isolate the fault zone or device and guarantee the systemsecurity. The primary protection and backup protection is in cooperation relationship, and backup one could not be canceled because of the DC power supply failure in substation. The fault location algorithm based on wide area information is one of the key points for novel wide area backup protection. By use of the synchronized phasor data uploaded by PMUs, the process of locating fault could be implemented in real-time or near real-time level. In this paper, based on Bayesian theory, we have studied the fault location in wide area backup protectionsystems. The simulation experiments have confirmed that the detection of fault can be resolved exactly and effectively by Bayesian theory.
The flywheel energy storage (FES) system presented in this paper is composed of four parts;the flywheel, the bearing, the motor/generator and the power converter. The control methods and strategy of the FES system in ...
详细信息
Combining electricity market dynamic model proposed by Alvarado, this paper uses differential/algebraic equations and eigenvalue techniques to study the stability of electricity markets. The necessary and sufficient c...
详细信息
ISBN:
(纸本)0863412467
Combining electricity market dynamic model proposed by Alvarado, this paper uses differential/algebraic equations and eigenvalue techniques to study the stability of electricity markets. The necessary and sufficient conditions of judging electricity market stability and asymptotical stability are provided. As well as the sufficient conditions of judging electricity market unstable and asymptotical unstability is presented. The obtained conclusions removed the condition of Yang's with the assumption "the matrix is square and nonsingular" and other conditions. Using these stability conditions may directly judge the electricity market model stability by the initial data. In addition, the theoretical results in this paper can be used to reasonably explain the unable phenomena of electricity market proposed by Alvarado.
The power frequency over-voltage of EHV power transmission lines in three operating conditions, i.e., capacity effect of unloaded line, unsymmetrical faults and load shedding is analyzed. The shunt reactor's funct...
详细信息
ISBN:
(纸本)0863412467
The power frequency over-voltage of EHV power transmission lines in three operating conditions, i.e., capacity effect of unloaded line, unsymmetrical faults and load shedding is analyzed. The shunt reactor's function to restrain the power frequency over-voltage is analyzed theoretically. Different compensation ratios and installment positions of shunt reactors are simulated in three operating conditions of 750 kV transmission lines through the software ATP/EMTP. From the simulation results, it is found that the shunt reactors can restrain the power frequency over-voltage in three operating condition effectively and the magnitude of the power frequency over-voltage will be lower with the compensation ratio of the shunt reactor becoming larger. In addition, when the shunt reactor is switched at the terminal of the transmission line, its effect restraining the power frequency voltage is the best compared with other two modes of connection in unloaded line with single power supply, unsymmetrical faults and load shedding. The method of operation for the shunt reactor is also discussed in this paper. Along with the expansion of the system capacity and the line's transmitted power, the method of operation that the shunt reactor is switched off from the system needs to be considered according to the powersystem's operation condition.
Asymmetric load is quite common in distribution network, the compensation of which is a serious problem under some situations. A novel integrated compensation method is put forward based on the principle of reactive p...
详细信息
This paper researches profoundly on the coordinated control of UPQC (Unified power Quality Conditioner). By analyzing the radical reasons of coupling effect between UPQC series unit and shunt unit, a simple and practi...
详细信息
In this paper, a simple parallel calculation cluster is built by PC and local area network. The power electric network is divided into several subnets according the method of path graph partitioning. Subnets are alloc...
详细信息
As a series FACTS device based on Voltage Source Converter (VSC), Static Series Synchronous Compensators (SSSC) can optimize power flow and improve powersystem stability by controlling the line impedance rapidly. Acc...
详细信息
The relation between the voltage at the end of the opened phase conductor (VATEOTOPC) and the sum voltage of the two healthy phases (SVOTTHP) are analyzed. An integrated criterion based on the relation is proposed to ...
详细信息
ISBN:
(纸本)0863416381
The relation between the voltage at the end of the opened phase conductor (VATEOTOPC) and the sum voltage of the two healthy phases (SVOTTHP) are analyzed. An integrated criterion based on the relation is proposed to determine the fault nature of single-phase faults. The integrated criterion is simple in scheme and can be realized easily. It can distinguish between temporary and permanent faults effectively and has good adaptability to load currents and fault distances. Simulation tests show that the conclusions in this paper are correct.