A fast electric field integral in time domain using the uneven discretization and the implicit scheme is proposed to calculate the switching electromagnetic transient at a substation. The switching transient currents ...
详细信息
A fast electric field integral in time domain using the uneven discretization and the implicit scheme is proposed to calculate the switching electromagnetic transient at a substation. The switching transient currents and the resultant radiated electromagnetic field are calculated. The propose d approach has the strength to model the bus system at a substation with a more complicated and realistic configuration that is difficult to simulate using the circuit-based method, because all the electromagnetic couplings within the bus system are included globally. The proposed method might be one of good candidates to predicate the EMI level at a substation.
Five-level active neutral-point-clamped (ANPC) converter is a newly emerging topology which can overcome the drawbacks of traditional neutral-point clamped (NPC) converters and flying-capacitor (FC) converters. Its dc...
详细信息
IPS has many special characteristics, such as using multi-phase, multi-frequency and hybrid AC/DC devices. As a result, existing electromagnetic transient simulators developed for powersystems on land do not apply to...
详细信息
Recently, several power grids of China came across low frequency oscillations which are difficult to explain by the traditional negative damping mechanism. Some researchers suggest that those oscillations be caused by...
详细信息
Recently, several power grids of China came across low frequency oscillations which are difficult to explain by the traditional negative damping mechanism. Some researchers suggest that those oscillations be caused by external periodic disturbances according to the forced oscillation mechanism. It takes no doubt that the oscillation source location (means locating the disturbances) is imperative and decisive to eliminate such a kind of oscillations. This paper proposes a location methodology based on Energy Supply on Port derived from the Port-controlled Hamiltonian theory. By calculating the energy injected to the network at corresponding ports, the oscillation sources can be effectively located, even in complicated systems containing various kinds of control devices such as governors and exciters. Different from the traditional methodology based on eigen-analysis, the proposed methodology is naturally decentralized without the dependency on global measurements. Case studies on the standard 4-machine 2-area system and the IEEE-118 bus system show the effectiveness and efficiency of the proposed methodology.
Lightning overvoltage protection is of great importance to the safety of UHV GIS. The widely used arresters can only suppress the magnitude of lightning overvoltage but lack efficiency on alleviating the steepness. In...
详细信息
In order to maintain the separability of different fault onsets, more characteristic parameters need to be used to establish the feature space with multiple possible faults. Usually, the dimensions of feature space ha...
详细信息
In order to maintain the separability of different fault onsets, more characteristic parameters need to be used to establish the feature space with multiple possible faults. Usually, the dimensions of feature space have a positive correlation with the number of faults. Describing multiple faults in visualization is more difficult and the classification bounds with hyperplanes are less convenient to realize. Therefore implementing dimensionality reduction approaches in original feature space is beneficial for fault diagnosis and prognostics. Multidimensional Scaling (MDS) has been widely studied and used for dimensionality reduction as well as Principal Component Analysis (PCA). When these methods are applied in the prognostics process, the effectiveness needs validation with the reason that the deterioration features in degradations are different from the faults onsets that in diagnostics. The paper analyzes the nonlinear dimensionality reduction methods including Self-Organizing Map (SOM) and Isometric feature mapping (Isomap). Based on the deterioration data in an engine, the effects of these methods are analyzed.
Due to the complex conditions in rotating machinery, the blades usually encounter fluctuating loads, and failures may occur in the operation. Blade vibration is rarely monitored in the practical rotating machinery in ...
Due to the complex conditions in rotating machinery, the blades usually encounter fluctuating loads, and failures may occur in the operation. Blade vibration is rarely monitored in the practical rotating machinery in power plants as the traditional blade vibration method using strain gauge method is hard to be applied in long-time and online monitoring. The blade tip timing method is a promising approach to monitor the blade vibration and several special sensors are developed to realize the online monitoring. Based on the traditional blade tip timing method, an improved approach is established in this work. The proposed method can modify the expected arriving time when the torsional vibration exists. The accuracy is therefore improved in the torsional vibration case. Then the blade vibration monitoring with the traditional blade tip timing method and the proposed method are carried out in the test rig in laboratory. The results validate that, the torsional vibration influences the expected arriving time, and the proposed method can modify the expected arriving time and improve the accuracy of the blade vibration monitoring.
Under the skin effect caused by the alternating electromagnetic field, the transmission line parameters changes with frequency, and different line resistivity, surge impedance, wave speed are presented in one line und...
详细信息
This paper analyzes the general process of power flow transferring and divides it into four parts: 1) the process of first phase selection after fault occurs;2) the process of selective action at the first time;3) the...
详细信息
This paper studies the fault current frequency spectrum characteristics of single phase ground fault in ungrounded distribution networks, and the fault location method based on it. Firstly, it analyzes the production ...