Fault locator for power distribution system with neutral non-effectively grounded should locate phase-to-phase fault and single-phase-to-ground fault respectively. For phase-to-phase fault, the point can be located by...
详细信息
To protect the environment and lower carbon dioxide emissions, conventional fossil-fuel generators tend to be replaced by renewable generation. The volatile and uncertain renewable generation, as well as the reduced p...
详细信息
This paper studies the fault current frequency spectrum characteristics of single phase ground fault in ungrounded distribution networks, and the fault location method based on it. Firstly, it analyzes the production ...
详细信息
Estimating low-frequency oscillation modes and the corresponding mode shapes based on ambient data from WAMS measurements has a promising prospect of application in power system analysis and control. The present appro...
详细信息
Impedance method and single terminal travelling wave method are analyzed in paper, applicable scope of optimized solution is presented. Impedance method is of high robustness but low accuracy. Single terminal travelli...
详细信息
In order to protect more turn-to-turn faults for the turbo-generator with only three lead-out terminals in the neutral side, this paper applies a new principle protection - negative sequence impedance directional prot...
详细信息
ISBN:
(纸本)9788986510119
In order to protect more turn-to-turn faults for the turbo-generator with only three lead-out terminals in the neutral side, this paper applies a new principle protection - negative sequence impedance directional protection of fault components for stator internal asymmetrical fault. By means of Multi-loop Method, all possible internal short-circuit faults and single branch shutdown faults of a 300MW turbo-generator are calculated to obtain the protection performance. Calculation and performance analysis show that, this new principle protection is superior to other existing protections in the aspect of sensitivity and protection range, especially for interturn faults of turbogenerator stator winding. In addition, it won't incorrectly trip on external faults. Thus, this new principle protection can provide safeguard of high quality for internal faults in turbo-generator with only three lead-out terminals in the neutral side.
The concept of a digital power system (DPS) is set forth in the paper. The definition, the contents, the function, the hardware and the software conditions for implementing it are discussed. Moreover, the necessary ba...
详细信息
The concept of a digital power system (DPS) is set forth in the paper. The definition, the contents, the function, the hardware and the software conditions for implementing it are discussed. Moreover, the necessary basic research work for implementing a DPS is also discussed. The DPS may be defined like this: the digital power system is the digital, figuration and real time description and reappearance of physical structure, technical characteristic, management system as well as personal information system of a real power system which is in operation. The DPS will be able to make a significant contribution to administrating and decision-making more scientifically, improving security and stability online, online making and implementing economical operation strategy and carrying out emergency and anti-fault control, etc.
Commutation failure (CF) is one of the major concerns in high-voltage direct current (HVDC) transmission system. Of many methods to mitigate CF, advancing firing angle is preferred one since it can be easily implement...
详细信息
Traditional operation rules depend on human experience, which are relatively fixed and difficult to fulfill the new demand of the modern power grid. In order to formulate suitable and quickly refreshed operation rules...
详细信息
Traditional operation rules depend on human experience, which are relatively fixed and difficult to fulfill the new demand of the modern power grid. In order to formulate suitable and quickly refreshed operation rules, a method of linear decision tree based on support samples is proposed for rule extraction in this paper. The operation rules extracted by this method have advantages of refinement and intelligence, which helps the dispatching center meet the requirement of smart grid construction.
The wind farm has only one NWP data point, which cannot accurately reflect the wind resources inside the wind farm. To solve the problem of a poor match between short-term wind power prediction numerical weather forec...
详细信息