Impedance method and single terminal travelling wave method are analyzed in paper, applicable scope of optimized solution is presented. Impedance method is of high robustness but low accuracy. Single terminal travelli...
详细信息
Commutation failure (CF) is one of the major concerns in high-voltage direct current (HVDC) transmission system. Of many methods to mitigate CF, advancing firing angle is preferred one since it can be easily implement...
详细信息
Traditional operation rules depend on human experience, which are relatively fixed and difficult to fulfill the new demand of the modern power grid. In order to formulate suitable and quickly refreshed operation rules...
详细信息
Traditional operation rules depend on human experience, which are relatively fixed and difficult to fulfill the new demand of the modern power grid. In order to formulate suitable and quickly refreshed operation rules, a method of linear decision tree based on support samples is proposed for rule extraction in this paper. The operation rules extracted by this method have advantages of refinement and intelligence, which helps the dispatching center meet the requirement of smart grid construction.
Uncertainty is not negligible in powersystems, it affects the generation, transmission and utilization of electricity. Especially in electricity markets, the randomness and variability of generation or load will caus...
详细信息
In this paper, the reliability of the rolling bearing fault feature extraction based on casing vibration signals is discussed. Through the fault simulation experiment of rolling bearing, the vibration data of the oute...
详细信息
Establishing a suitable closed-loop transfer function model for the grid-connected PMSG system is the key basis in performing inter-harmonic characteristics *** closed-loop transfer functions can be constructed when d...
详细信息
Establishing a suitable closed-loop transfer function model for the grid-connected PMSG system is the key basis in performing inter-harmonic characteristics *** closed-loop transfer functions can be constructed when different components of the converter controller are taken into ***,the effect of different components of the converter controller on inter-harmonic stability analysis is not *** this paper,the complete transfer function,considering different loops,is first *** on the complete closed-loop transfer function,the DC-link,PLL and voltage forward-feed are removed step by step to derive different closed-loop transfer *** inter-harmonic related poles of different closed-loop transfer functions are further calculated to analyze the effect of closedloop transfer functions on inter-harmonic characteristics ***,by performing time domain simulation,the correctness of the theoretical analysis results is *** results show that under the conditions of a weak AC system,each loop of the converter control system will reduce the stability of the interharmonic in the sub-synchronous frequency range and influence the inter-harmonic oscillation *** transfer function needs to consider the influence of each loop to accurately calculate the inter-harmonic stability of the system.
Time-varying frequency selective attenuation and colored noises are unfavorable characteristics of power line communication(PLC) channels of the low voltage *** overcome these disadvantages,a novel real-time dynamic s...
详细信息
Time-varying frequency selective attenuation and colored noises are unfavorable characteristics of power line communication(PLC) channels of the low voltage *** overcome these disadvantages,a novel real-time dynamic spectrum management(DSM) algorithm in orthogonal frequency division multiplexing(OFDM)-based high-speed narrow-band power line communication(HNPLC) systems is proposed,and the corresponding FPGA circuit is designed and *** of the proposed DSM is validated with a large amount of network experiments under practical PLC *** the noise in each narrow subcarrier is approximately Gaussian,the proposed DSM adopts the BER/SER expression formulized via the AWGN channel to provide a handy and universal strategy for power *** real-time requirement is guaranteed by choosing subcarriers in group and employing the same modulation scheme within each *** measures are suitable for any modulation scheme no matter the system criterion is to maximize data rate or minimize power/*** design and hardware implementation of the proposed DSM are given with some flexible and efficient *** DSM circuit is carried out with Xilinx *** and practical experiments validate that the proposed real-time DSM significantly improves system performance.
To coordinately consider the economy and security of the system during reactive voltage control, a multi-objective reactive power optimization model is proposed. Apart from the conventional economic objective, the new...
详细信息
With the continuous advancement of the construction of new powersystems, the data information of the power system is increasing exponentially, and the spatiotemporal distribution of the use of smart terminals and ele...
详细信息
In LCC-HVDC hybrid grid, commutation failure is an important factor affecting system stability. When there is a fault or a large voltage fluctuation in AC line of LCC-HVDC, a commutation failure will occur. Fault curr...
详细信息